Deterministic engineering monitor

C-FOMS Design Basis Monitor

Signed boiler stress, cycle-range monitoring and bounded maintenance recommendations based on 9915-370-102-PVM-W-053.

Internal stress unit: MPa Pressure input: kg/cm² Negative = compression AI cannot change calculations Open calculation validator
No dataset loaded
±
Why can thermal stress be negative?
The app uses Δt = Tmetal − Tsteam. During heat-up, steam normally leads the mean metal temperature, so Δt and bore thermal stress are negative (compression). The governing PDF’s cold-start annexure shows −272.71 MPa. Fatigue uses the full signed stress range; replacing Δt with ABS(Δt) gives the wrong cycle.
Analysed
configured components
Alarm / Watch
deterministic status
Life status
no unsupported percentage
Advisory mode
AI is optional

Component stress status

Equation 6 signed tangential stress = pressure + thermal

Load a dataset and run the analysis.

Governing-document cold-start benchmark

Annexure 2, T92 header/stub geometry. This test is recomputed by the application on every verification run.

QuantityDocumentCalculatedCheck

NIMS Grade 91 tube creep-reference validation

Mean material-data regression only. It is not an EN 12952 allowable, a weldment curve, or a commissioned remaining-life result.

Loading benchmark…